Carry out measurements without any annoying cables: use the kit to handle all relevant measurements in ventilation ducts and at air/ceiling outlets. You will receive the testo 440 dP air velocity and IAQ measuring instrument including differential pressure sensor, two vane probe heads (Ø 100 mm and Ø 16 mm) and a humidity/temperature probe head – all three can be attached to the universal Bluetooth® handle supplied. To make measurements more convenient, both vane probe heads can be combined with the telescope included in the kit. The equipment can be transported safely and conveniently in the robust case.
: 0560 4101
testo 410-1 - Vane anemometer
: 0560 4102
testo 410-2 - Vane anemometer
: 0563 4410
testo 440 delta P Air Flow ComboKit 2 with Bluetooth®
: 0563 4403
testo 440 100 mm Vane Kit with Bluetooth®
: 0563 4406
testo 440 Air Flow ComboKit 1 with Bluetooth®
: 0563 4401
testo 440 16 mm Vane Kit
Temperature - NTC | Measuring range −40 to +150 °C |
|---|---|
Accuracy ±0,4 °C (+75 to +99,9 °C) ±0,4 °C (−40 to −25,1 °C) ±0,5 % of mv (Remaining Range) ±0,3 °C (−25 to +74,9 °C) | |
Resolution 0,1 °C | |
Temperature - TC Type K (NiCr-Ni) | Measuring range −200 to +1370 °C |
|---|---|
Accuracy ±(0,3 °C + 0,3 % of mv) | |
Resolution 0,1 °C | |
Differential pressure (internal sensor) - Piezoresistive | Measuring range −150 to +150 hPa |
|---|---|
Accuracy ±0,05 hPa (0 to 1,00 hPa) (1,01 to +150 hPa) ±0,2 hPa + 1,5 % of mv | |
Resolution 0,01 hPa | |
General technical data | Weight 250 g |
|---|---|
Dimensions 154 x 65 x 32 mm | |
Operating temperature −20 to +50 °C | |
Connectable probes 1 x digital probe with cable or 1 x Temperature NTC TUC, 1 x digital Bluetooth probe or testo Smart Probe, 1 x differential pressure (internal), 1 x Temperature TC Type K | |
Product colour black/orange | |
Battery life 12 h (typically vane measurement) | |
Battery type 3 AA mignon 1.5 V | |
Interface Bluetooth®; USB | |
Storage temperature −20 to +50 °C | |
General technical data | Storage temperature -20 to +60 °C |
|---|---|
Weight 360 g | |
Dimensions 375 x 105 x 46 mm | |
Operating temperature -5 to +50 °C | |
Probe head diameter 100 mm | |
Product colour black/orange | |
Battery type 4 x type AA batteries | |
Battery life 60 h | |
Data transfer Bluetooth® | |
Radio range 20 m | |
Temperature - NTC | Measuring range -20 to +70 °C |
|---|---|
Accuracy ±0,5 °C | |
Resolution 0,1 °C | |
Velocity / Volume flow | Measuring range 0,3 to 35 m/s |
|---|---|
Accuracy ±(0,2 m/s + 1,5 % of mv) (20,01 to 35 m/s) ±(0,1 m/s + 1,5 % of mv) (0,3 to 20 m/s) | |
Resolution 0,01 m/s | |
Temperature - NTC | Measuring range -10 to +70 °C |
|---|---|
Accuracy ±1,8 °C | |
Resolution 0,1 °C | |
Velocity / Volume flow | Measuring range 0,6 to 50 m/s |
|---|---|
Accuracy ±(0,2 m/s + 1 % of mv) (0,6 to +40 m/s) ±(0,2 m/s + 2 % of mv) (40,1 to 50 m/s) | |
Resolution 0,1 m/s | |
General technical data | Storage temperature -10 to +70 °C |
|---|---|
Weight 60 g | |
Dimensions 245 x 16 x 16 mm | |
Operating temperature -10 to +70 °C | |
Length probe shaft 230 mm | |
Diameter probe shaft 16 mm | |
Probe head diameter 16 mm | |
Product colour Black | |
Temperature - NTC | Measuring range -20 to +70 °C |
|---|---|
Accuracy ±0,5 °C | |
Resolution 0,1 °C | |
Humidity - Capacitive | Measuring range 0 to 100 %RH |
|---|---|
Accuracy long-term stability: ±1 %RH / year ±0,03 %RH/K (k=1) ±2 %RH (5 to 90 %RH) | |
Resolution 0,1 %RH | |
General technical data | Storage temperature -20 to +70 °C |
|---|---|
Weight 30 g | |
Dimensions 160 x 28 x 28 mm | |
Operating temperature -20 to +70 °C | |
Diameter probe shaft 12 mm | |
Length probe shaft 140 mm | |
Product colour Black | |
General technical data | Weight 155 g |
|---|---|
Dimensions angle: 65 x 65 x 15 mm teleskop: 375 x 17 x 16 mm | |
Operating temperature -5 to +50 °C | |
Length telescope 1.000 mm | |
Diameter telescope 12 mm | |
Product colour Black | |
Storage temperature -20 to +60 °C | |
General technical data | Weight 1400 g |
|---|---|
Dimensions 516 x 135 x 256 mm | |
Product colour Black | |