Use the 100 mm vane/temperature probe to determine flow velocity or volume flow at ventilation outlets. Integrated temperature measurement enables the vane anemometer to measure temperatures up to +50 °C.
For convenient, accurate measurements at plate outlets and ventilation grilles, we recommend that you use the vane/temperature probe in conjunction with the testo 435 measuring instrument and the testovent 417 funnel set (both optionally available). This guarantees simple testing of incoming/outgoing air – such as in the controlled ventilation of living spaces.
If you add in the testovent 417 volume flow straightener (optional), you can achieve an impressively high level of precision when carrying out measurements at swirl outlets.
General technical data
General technical data
Diameter
100 mm
Temperature - NTC
Temperature - NTC
Measuring range
0 to +50 °C
Accuracy
±0.5 °C
Velocity / Volume flow
Velocity / Volume flow
Measuring range
+0.3 to +20 m/s
Accuracy
±(0.1 m/s + 1.5 % of mv)
Vane/temperature probe (Ø 100 mm) with fixed cable 1.8 m.