Kit for carrying out measurements in ventilation ducts: the testo 440 air velocity and IAQ measuring instrument and the vane probe (Ø 16 mm) are safely stowed away in the case. So you can get down to work straight away!
: 0560 4101
testo 410-1 - Vane anemometer
: 0560 4102
testo 410-2 - Vane anemometer
: 0563 4410
testo 440 delta P Air Flow ComboKit 2 with Bluetooth®
: 0563 4403
testo 440 100 mm Vane Kit with Bluetooth®
: 0563 4406
testo 440 Air Flow ComboKit 1 with Bluetooth®
: 0563 4401
testo 440 16 mm Vane Kit
Temperature - NTC | Measuring range −40 to +150 °C |
|---|---|
Accuracy ±0,4 °C (+75 to +99,9 °C) ±0,4 °C (−40 to −25,1 °C) ±0,5 % of mv (Remaining Range) ±0,3 °C (−25 to +74,9 °C) | |
Resolution 0,1 °C | |
Temperature - TC Type K (NiCr-Ni) | Measuring range −200 to +1370 °C |
|---|---|
Accuracy ±(0,3 °C + 0,3 % of mv) | |
Resolution 0,1 °C | |
General technical data | Weight 250 g |
|---|---|
Dimensions 154 x 65 x 32 mm | |
Operating temperature −20 to +50 °C | |
Connectable probes 1 x digital probe with cable or 1 x Temperature NTC TUC, 1 x digital Bluetooth probe or testo Smart Probe, 1 x Temperature TC Type K | |
Product colour black/orange | |
Battery type 3 AA mignon 1.5 V | |
Battery life 12 h (typically vane measurement) | |
Interface Bluetooth®; USB | |
Storage temperature −20 to +50 °C | |
Velocity / Volume flow | Measuring range 0,6 to 50 m/s |
|---|---|
Accuracy ±(0,2 m/s + 2 % of mv) (40,1 to 50 m/s) ±(0,2 m/s + 1 % of mv) (0,6 to 40 m/s) | |
Resolution 0,1 m/s | |
General technical data | Storage temperature -10 to +70 °C |
|---|---|
Weight 150 g | |
Dimensions 330 x 16 x 16 mm | |
Operating temperature -10 to +70 °C | |
Cable length 1,7 m | |
Length telescope 850 mm | |
Probe head diameter 16 mm | |
Diameter telescope 12 mm | |
Product colour Black; silver | |