A measuring instrument for all climate-related parameters
-
Intuitive: clearly structured measurement menu for volume flow and parallel determination of air velocity, humidity and temperature in ventilation ducts or at ventilation outlets
-
Clever: hot wire probe with telescope (0.85 m) – combine the vane probe (Ø 100 mm) with Bluetooth with the telescope for ceiling outlets or the funnel set for plate outlets (please order separately) as required
-
Extendible with a wide range of probes
-
Wireless measurement with Bluetooth probes
-
USB interface for exporting measurement reports as CSV files
-
Temperature - NTC Measuring range
-40° to 302 °F / -40 to +150 °C
Accuracy
±0.7 °F (-40° to -13.2 °F) / ±0.4 °C (-40 to -25.1 °C)
±0.5 °F (-13° to 166.8 °F) / ±0.3 °C (-25 to +74.9 °C)
±0.7 °F (167° to 211.8 °F) / ±0.4 °C (+75 to +99.9 °C)
±0.5 % of mv (Remaining Range)
Resolution
0.1 °F / 0.1 °C
Temperature - Type K TC Measuring range
-328.0° to 2498.0 °F / -200 to +1370 °C
Accuracy
±(0.5 °F + 0.3 % of mv) / ±(0.3 °C + 0.3 % of mv)
Resolution
0.1 °F / 0.1 °C
General technical data Weight
8.8 oz. / 250 g
Dimensions
6.1 x 2.6 x 1.3 in. / 154 x 65 x 32 mm
Operating temperature
-4.0° to 122.0 °F / -20 to +50 °C
Connectable probes
1 x digital probe with cable or 1 x Temperature NTC TUC, 1 x digital Bluetooth probe or testo Smart Probe, 1 x Temperature TC Type K
Product colour
black/orange
Battery type
3 x AA 1.5 V
Battery life
12 h (typically vane measurement)
Interface
Bluetooth®; USB
Storage temperature
-4.0° to 122.0 °F / -20 to +50 °C
-
General technical data Storage temperature
-4° to 140 °F / -20 to +60 °C
Weight
12.7 oz. / 360 g
Dimensions
14.8 x 4.1 x 1.8 in. / 375 x 105 x 46 mm
Operating temperature
23° to 122 °F / -5 to +50 °C
Probe head diameter
3.937 in. / 100 mm
Product colour
black/orange
Battery type
4 x AA batteries
Battery life
60 h
Data transfer
Bluetooth®
Radio range
65.616 ft. / 20 m
Temperature - NTC Measuring range
-4° to 158 °F / -20 to +70 °C
Accuracy
±0.9 °F / ±0.5 °C
Resolution
0.1 °F / 0.1 °C
Velocity / Volume flow Measuring range
59.1 to 6890 fpm / 0.3 to 35 m/s
Accuracy
±(7 fpm + 5% of mv) (59 to 6890 fpm) / ±(0.1 m/s + 1.5 % of mv) (0.3 to 20 m/s)
±(0.04 m/s + 5 % of mv) (0.3 to 35 m/s) / ±(0.2 m/s + 1.5 % of mv) (20.01 to 35 m/s)
Resolution
1 fpm / 0.01 m/s / 0.01 m/s
-
Temperature - NTC Measuring range
-4° to 158 °F / -20 to +70 °C
Accuracy
±0.9 °F / ±0.5 °C
Resolution
0.1 °F / 0.1 °C
Absolute Pressure Measuring range
+280 to +440 InH₂O / +700 to +1100 hPa
Accuracy
±1.2 InH₂O / ±3.0 hPa
Resolution
0.1 InH₂O / 0.1 hPa
Velocity - Hot wire anemometer Measuring range
0 to 5906 fpm / 0 to 30 m/s
Accuracy
±(5.91 fpm + 4 % of mv) / ±(0.03 m/s + 4 % of mv)
(0 to 3937 fpm) / (0 to 20 m/s)
±(98.4 fpm + 5 % of mv) / ±(0.5 m/s + 5 % of mv)
(3938.98 to 5906 fpm) / (20.01 to 30 m/s)
Resolution
1.97 fpm / 0.01 m/s
General technical data Storage temperature
-4° to 158 °F / -20 to +70 °C
Weight
3.2 oz. / 90 g
Dimensions
12.4 x 0.5 x 0.5 in. / 315 x 12 x 12 mm
Operating temperature
-4° to 158 °F / -20 to +70 °C
Cable length
5.577 ft.
Length telescope
33.465 in. / 850 mm
Probe head diameter
0.354 in. / 9 mm
Diameter telescope
0.472 in. / 12 mm
Product colour
Black; silver
Diameter probe shaft
0.472 in. / 12 mm
-
General technical data Weight
49.4 oz. / 1400 g
Dimensions
20.3 x 5.3 x 10.1 in. / 516 x 135 x 256 mm
Product colour
Black